Custom Copper GIS Contact Housing with Internal Grooves and Side Branch
Video
Short Description
Custom copper GIS contact housing featuring a hollow cylindrical body, internal circumferential grooves, a side branch boss with four mounting holes, and a circular opening on the opposite wall. The component can be configured for drawing-specific busbar and switchgear connection assemblies.
Material options include C10200, C10100, and C11000 copper, with alternative copper alloys reviewed according to electrical and mechanical requirements. Bore dimensions, groove geometry, branch alignment, radial threads, edge radii, and surface treatments are confirmed against the approved drawing.
Product Overview
A copper GIS contact housing is a conductive component used to locate and connect mating conductors within an engineered switchgear assembly. This design combines an axial tubular contact region with a lateral connection interface.
The illustrated component has internal annular grooves near the bore openings, rounded end rims, a projecting cylindrical branch boss, four holes on the branch end face, and smaller radial tapped holes. A circular opening opposite the branch provides access to the interior; its intended assembly function must be established by the equipment drawing.
Material selection starts with the required conductivity, hardness, operating temperature, and contact arrangement. Cymber Metal’sPure Copperrange provides a starting point for reviewing suitable copper materials, while itsFine Machiningservices support drawing-based component discussions.
This product is an internal conductive contact housing, not automatically a gas-tight pressure enclosure or a copper plumbing fitting. Current rating, insulation performance, and equipment compatibility depend on the completed assembly.
Product Specifications
The following values are reference requirements from the product brief, not measurements of the photographed sample or guaranteed limits for every design. Size combinations, tolerances, and inspection methods require engineering confirmation.
| Parameter | Reference Specification / Order Requirement |
|---|---|
| Product Type | Custom tubular copper contact housing with lateral branch boss |
| Main Body Geometry | Hollow cylindrical body with open axial ends |
| Internal Features | Circumferential grooves and stepped bore features according to drawing |
| Branch Interface | Side cylindrical boss with four-hole end-face pattern |
| Opposite-Wall Opening | Circular access opening; diameter and location to drawing |
| Additional Holes | Radial tapped holes; thread size, depth, and position to drawing |
| Primary Material Options | C10200 oxygen-free copper, C10100 oxygen-free electronic copper, or C11000 ETP copper |
| Alternative Materials | C10400 or C10700 silver-bearing copper; C18150 CuCrZr subject to application review |
| Material Standard | Selected according to copper grade, starting form, and purchase specification |
| Main Body Outside Diameter | Reference design range: 40–320 mm |
| Main Bore Diameter | Reference design range: 25–260 mm |
| Main Body Length | Reference design range: 60–600 mm |
| Bore / Groove-Root Diameter Tolerance | Reference target: ±0.015 to ±0.03 mm on designated features |
| End-to-End Bore Coaxiality | Reference target: ≤0.02 mm; datum and evaluation method required |
| Branch Alignment | Reference target: ≤0.025 mm; controlled feature and datum scheme to be defined |
| Functional Surface Roughness | Reference target: Ra 0.2–0.4 μm; specify the maximum permitted value for each surface |
| Hardness | Reference range: 85–135 HV; dependent on grade, condition, and test location |
| Electrical Conductivity | Grade- and condition-specific acceptance value to be agreed |
| Surface Options | Bare copper, agreed anti-tarnish treatment, silver plating, tin plating, or nickel plating |
| Silver Plating Thickness | Reference option: 10–30 μm on specified surfaces |
| Documentation | Material and inspection documents according to the purchase order |
Dimensions within the reference ranges cannot be combined arbitrarily. Wall thickness, branch proportions, machining access, and structural requirements must be reviewed together.
Key Features
| Feature | Design Relevance |
|---|---|
| Tubular Main Body | Provides an axial interface for mating conductive components |
| Internal Circumferential Grooves | Can accommodate specified contact bands or other retaining features when designed for the selected system |
| Four-Hole Branch Boss | Provides a drawing-defined lateral mounting or conductive connection interface |
| Opposite Access Opening | Can facilitate internal assembly access where confirmed by the equipment design |
| Radial Tapped Holes | Allow drawing-specific fastening or positioning arrangements |
| Rounded End Rims | Provide controlled entry geometry for mating parts |
| Curved Branch Transition | Allows the external junction geometry to be defined for machining, assembly, and electrical design requirements |
| Optional Contact Coatings | Allow surface treatment to be matched to the mating contact system and operating environment |
Rounded edges and controlled surface finish support the assembly design, but do not independently establish partial-discharge performance or a voltage rating.
Manufacturing Process
The manufacturing route is selected from the approved geometry, material condition, quantity, and inspection requirements. A specific five-axis machine, single-setup sequence, or one-piece construction should be stated only when confirmed in the production plan.
| Stage | Process Scope | Main Control Point |
|---|---|---|
| Drawing Review | Review bore geometry, groove sections, branch interface, access opening, and mating components | Confirm functional dimensions, datums, and coating allowance |
| Material Selection | Select the specified copper grade and suitable starting stock or near-net blank | Verify material identity and required condition |
| Blank Preparation | Prepare machining allowances and initial reference surfaces | Maintain sufficient material around the branch and main bore |
| Main Body Machining | Turn and bore the cylindrical body and axial interfaces | Control bore size, wall thickness, and datum relationships |
| Internal Groove Machining | Produce the specified annular grooves and entry features | Control groove width, root diameter, spacing, and edge condition |
| Branch and Opening Machining | Machine the branch face, four-hole pattern, opposite opening, and radial threads | Control positions and orientation relative to the approved datums |
| Edge Finishing | Deburr accessible and intersecting features; produce specified radii | Inspect internal edges and contact-entry regions |
| Surface Treatment | Apply agreed coating or copper-surface protection | Account for coating thickness on functional dimensions |
| Final Inspection and Packing | Complete agreed checks, clean the component, and protect finished surfaces | Prevent contamination, impact damage, and coating damage |
Surface-treatment requirements can be reviewed through theBusbar Plating Shop. Internal grooves may require specific masking, coverage, and thickness-verification arrangements.
Manufacturing & Quality Control
Inspection should concentrate on the mating bore, contact-band grooves, branch interface, hole pattern, and internal edge condition. The inspection scope and acceptance criteria should be agreed before production.
| Inspection Item | Proposed Method / Control | Acceptance Basis |
|---|---|---|
| Material Identity | Review material documentation and conduct appropriate composition checks when required | Specified copper grade and material standard |
| Oxygen Content | Use suitable oxygen-analysis documentation or testing when oxygen content is specified | Grade-specific oxygen requirement; routine composition testing alone is insufficient |
| Conductivity | Use a suitable conductivity test method with defined temperature correction and specimen conditions | Agreed value for the selected grade and condition |
| Main Bore Dimensions | Bore gauges, suitable internal measuring equipment, or CMM where accessible | Approved bore dimensions and tolerances |
| Internal Groove Geometry | Suitable groove gauges, dimensional probes, or agreed specialist measurement | Groove root diameter, width, spacing, and edge profile |
| Bore Alignment | Datum-based measurement using suitable equipment | Agreed end-to-end alignment requirement |
| Branch Orientation | CMM or another approved geometric inspection method | Drawing-defined feature relationship and datums |
| Four-Hole Pattern | Dimensional inspection of hole size, spacing, and position | Approved branch-interface drawing |
| Radial Threads | Thread gauges and depth checks where applicable | Specified thread designation, class, and depth |
| Surface Roughness | Roughness measurement on designated, accessible surfaces | Surface-specific Ra limit |
| Internal Edge Condition | Visual inspection, magnification, or borescope inspection as appropriate | Agreed deburring and edge-radius requirements |
| Hardness | Suitable Vickers hardness testing at an agreed location | Specified grade, condition, and hardness range |
| Plating | Agreed thickness, coverage, adhesion, and appearance checks | Coating specification and inspection plan |
| Internal Integrity | Ultrasonic or other suitable examination when specified and technically applicable | Agreed method, coverage, and acceptance criteria |
| Traceability and Records | Maintain the agreed relationship between material, production batch, and inspection records | Purchase-order documentation requirements |
SeeQuality Assurancefor Cymber Metal’s quality-support information. EN 10204 3.1 documentation, first-article reports, and third-party inspection should be specified during quotation rather than assumed for every shipment.
Typical Applications
These are potential application categories. Suitability must be established by the equipment designer using the actual component geometry, mating contacts, operating conditions, and qualification requirements.
| Application | Potential Component Role | Main Confirmation Requirements |
|---|---|---|
| GIS Busbar Branch Assemblies | Conductive housing connecting axial busbar contacts to a lateral interface | Current duty, contact arrangement, insulation clearances, and electric-field design |
| Circuit-Breaker Connection Assemblies | Drawing-specific conductive connection or contact-support component | Mechanical interface, temperature rise, operating forces, and assembly compatibility |
| Disconnector Contact Assemblies | Housing for specified contact bands and mating conductors | Contact pressure, insertion force, coating, alignment, and operating travel |
| Earthing-Switch Assemblies | Engineered conductive contact or connection component | Short-time current duty, contact engagement, and mechanical loading |
| Gas-Insulated Line Nodes | Internal conductive branch or transition component | Conductor geometry, support arrangement, insulation system, and thermal performance |
| Custom High-Current Connectors | Tubular contact housing with a lateral bolted interface | Joint resistance, bolt arrangement, mating surfaces, and thermal cycling |
The component’s appearance alone does not establish a voltage class or compliance with an IEC equipment standard.
Frequently Asked Questions
A copper GIS contact housing is an internal conductive component used in a gas-insulated switchgear connection assembly. This version combines a tubular main body, internal annular grooves, and a lateral branch interface. Its precise function depends on the mating conductors and contact system. It should not be confused with the external gas-tight GIS enclosure.
A standard copper pipe tee is generally designed for fluid connections. This component has electrical-contact features, including internal grooves, a four-hole branch face, and radial tapped holes. Its dimensions and finishes are controlled around electrical and mechanical interfaces. It is not interchangeable with a plumbing tee, and no pressure rating should be inferred.
C10200, C10100, and C11000 are the primary options identified for review. Selection depends on conductivity, oxygen-related requirements, mechanical condition, and the applicable material specification. Silver-bearing copper or C18150 CuCrZr may be considered where the design requires different strength or softening resistance, but these are not equivalent substitutes and require separate property confirmation.
The grooves can be designed for a specified louvered or multi-contact band system. Compatibility requires the selected band’s installation dimensions, mating-conductor diameter, coating allowance, and operating requirements. A photograph or generic groove description is insufficient to confirm fit. The contact-band specification should be supplied with the housing drawing.
The brief identifies reference bore and groove-root diameter tolerances of ±0.015 to ±0.03 mm, with an end-to-end bore coaxiality target of ≤0.02 mm. These values require review against component size, wall thickness, datum structure, coating allowance, and measurement access. They should be assigned to specific drawing features rather than applied universally.
Silver plating can be reviewed for specified contact surfaces, including internal grooves where the process is suitable. The brief gives 10–30 μm as a reference thickness option. The order should define coating composition, hardness if relevant, local thickness requirements, coverage, masking, and post-plating dimensions. Tin, nickel, or an agreed bare-copper finish may also be considered.
No. Suitability depends on the complete equipment design and qualification. Important factors include electric-field distribution, insulation clearances, contact resistance, temperature rise, mechanical loads, and short-time current duty. Where IEC 62271 requirements apply, the relevant equipment or assembly must be evaluated accordingly. Machining accuracy and copper grade alone do not establish compliance.
Please provide a dimensioned drawing, available 3D model, copper grade, material condition, quantity, mating-contact details, critical tolerances, and surface-treatment requirements. Also identify operating conditions, required inspection documents, destination, and target delivery date. For internal contact-band grooves, include the selected contact-system specification and clarify whether dimensions apply before or after plating.
Request a Quote
| RFQ Item | Information to Provide |
|---|---|
| Drawing Package | Dimensioned 2D drawing and available STEP or other agreed 3D model |
| Material | Copper grade, standard, condition, and any oxygen-content requirement |
| Main Dimensions | Body OD, bore ID, length, wall thickness, and branch dimensions |
| Internal Grooves | Section geometry, root diameter, width, spacing, and mating contact-band specification |
| Branch Interface | Four-hole pattern, hole type, face requirements, and orientation |
| Other Features | Access-opening dimensions, radial threads, chamfers, and edge radii |
| Tolerances | Functional dimensions, datum scheme, geometric tolerances, and inspection method |
| Electrical Requirements | Conductivity, current duty, operating temperature, and relevant assembly requirements |
| Surface Treatment | Coating type, thickness, coverage, masking, and final dimensional requirements |
| Quantity | Prototype quantity, batch quantity, and expected repeat demand |
| Quality Documents | Material documents, dimensional report, first-article inspection, or third-party inspection |
| Delivery | Destination, packing requirements, and target schedule |
Contact Uswith your drawing and specifications to review material selection, machining feasibility, surface treatment, inspection scope, and quotation requirements.