Custom Dual-Stud Copper Blade Contact Terminal
Video
Short Description
Custom copper blade contact terminal featuring a rounded blade head, central flange and two stepped threaded studs with axial internal tapped holes. Designed for drawing-matched switchgear, bushing and high-current connection assemblies. Material options include C11000, C10200 and C10100, with monoblock machining, thread geometry, contact-face finish and selective plating specified to suit the application. Final dimensions, tolerances and inspection requirements are confirmed against the approved drawing.
Copper Blade Contact Terminal Overview
A copper blade contact terminal combines a blade-shaped electrical interface with threaded mounting and connection features. This dual-stud design incorporates an elongated rounded blade, a supporting flange and two parallel stems with external threads and internal tapped holes.
The two-stem arrangement can support positional restraint when used with a suitably designed mating component. External and internal threads provide separate interfaces, but their functions, engagement lengths and tightening requirements must be defined by the assembly drawing.
Cymber Metal supports drawing-based terminals using selectedpure copper materials. C11000 is an ETP copper option, whileC10200 oxygen-free copperand C10100 can be reviewed where an oxygen-free grade is required.
For a specified monoblock construction, the blade, flange and studs are machined from a common blank rather than assembled using separately welded studs. This removes that particular welded interface, but thread strength, contact resistance and short-circuit performance still require appropriate design and validation.
This product is a conductive component, not a complete circuit breaker or insulating bushing. Electrical ratings and equipment suitability are determined at the assembly level.
Key Features
| Feature | Practical Value |
|---|---|
| Rounded Blade Head | Provides a defined mating profile and lead-in geometry; insertion behavior depends on the complete contact arrangement |
| Dual Threaded Studs | Provides two mounting locations and can support resistance to rotation in a properly designed mating assembly |
| Internal and External Threads | Allows separate mounting and connection interfaces where the assembly design requires them |
| Monoblock Construction | Avoids a separate welded stud joint within the specified component |
| Stepped Shoulders and Flange | Provides drawing-defined seating surfaces and assembly references |
| Controlled Contact Faces | Allows blade thickness, surface finish and coating coverage to be matched to the mating contact |
| Material and Finish Options | Enables review of conductivity, thread strength, wear and environmental requirements |
Manufacturing & Quality Control
Manufacturing Process
The manufacturing route is selected around the component drawing, material condition and critical interfaces.
| Stage | Process and Control |
|---|---|
| Drawing Review | Confirm blade geometry, flange dimensions, stud spacing, internal and external threads, datums and functional surfaces |
| Material Selection | Select the copper grade, temper and starting form; oxygen-free processing is specified only for the appropriate oxygen-free grades |
| Blank Preparation | Prepare a suitable wrought blank; near-net forming or forging may be considered where geometry and quantity justify it |
| CNC Machining | Use drawing-basedcopper machining supportto produce the blade, flange, shoulders and studs |
| Thread Production | Machine external and internal threads using methods appropriate to the size, access and required fit |
| Edge and Root Finishing | Control blade edges, thread entrances, undercuts and stud-root geometry according to the drawing |
| Surface Treatment | Review selective or fullcopper component platingagainst contact, assembly and environmental requirements |
| Cleaning and Packaging | Clean the finished component and protect the blade faces, threads and seating surfaces during shipment |
Quality Control
Inspection scope, frequency and acceptance criteria are agreed before production. Further information is available on thequality assurancepage.
| Inspection Item | Verification and Acceptance Basis |
|---|---|
| Material Identification | Review material certificates and maintain the agreed batch identification |
| Chemical Composition | Verify against the specified grade using suitable methods; oxygen-content requirements need an appropriate dedicated test |
| Blade and Flange Dimensions | Inspect blade thickness, outline, flange dimensions and defined seating surfaces |
| Stud Geometry | Check center distance, shoulder dimensions and alignment against the specified datums |
| Internal and External Threads | Use suitable thread gauges and supplementary measurements; final acceptance must account for any coating |
| Geometric Alignment | Verify specified thread-axis alignment, stud perpendicularity and related geometric requirements |
| Contact-Face Finish | Measure roughness where required and inspect for relevant burrs, dents or other surface defects |
| Conductivity and Hardness | Test where ordered, with material condition, method and acceptance values defined in advance |
| Coating Quality | Check specified thickness, coverage and relevant coating properties |
| Additional Testing | Nondestructive testing or joint-performance checks may be agreed where technically appropriate |
| Documentation | Supply agreed material and dimensional records; EN 10204 3.1 documentation or third-party inspection requires advance confirmation |
Component inspection does not replace equipment-level temperature-rise, dielectric, mechanical-endurance or short-circuit verification.
Typical Applications
The following are potential drawing-matched applications, not universal compatibility claims.
| Application | Typical Use | Design Considerations |
|---|---|---|
| Draw-Out Switchgear | Stationary blade-contact terminal within a matching contact assembly | Blade engagement, contact pressure, alignment, coating wear and temperature rise |
| Insulating Bushing Assemblies | Conductive terminal connected through or alongside a designed insulating support | Stud spacing, mounting loads, insulation geometry and electric-field distribution |
| Circuit Breaker Connections | Custom conductive interface for a specified breaker assembly | Mechanical compatibility, contact resistance, service duty and equipment verification |
| Traction and Power Conversion Equipment | High-current terminal for drawing-specific conductor connections | Vibration, installation torque, thermal cycling and connection design |
| Renewable Energy and Energy Storage Equipment | Custom terminal between busbars and electrical assemblies | Current duty, available space, corrosion exposure and validated temperature rise |
| Industrial Electrode Connections | Conductive connector for suitable heating or electrode equipment | Operating temperature, current duty and mechanical loading; fluid service requires a separate design |
FAQ
It is a conductive component combining a blade-shaped contact interface with two threaded stems. In this design, the stems also contain internal tapped holes for drawing-defined connection functions.
Yes. Blade thickness, outline, flange geometry, stud spacing and shoulder dimensions can be reviewed against the mating assembly. Critical dimensions and inspection datums should be identified on the drawing.
It can provide positional restraint when both studs engage a suitably designed mating component. Performance depends on hole clearance, support stiffness, fastening arrangement and applied torque; the component alone does not guarantee anti-rotation.
Yes, where the assembly is designed for this arrangement. Thread sizes, engagement depths and remaining stud wall must be checked together, along with tightening loads and the intended current path.
C11000, C10200 and C10100 can be considered according to conductivity, material condition and processing requirements. Alternative copper alloys require a separate review because strength, wear behavior and conductivity will differ.
Selective silver plating can be reviewed for specified contact surfaces. Define coating thickness, hardness, underlayer, coverage and masking requirements. Plating does not independently establish the current rating or service life.
The photographs show internal tapped holes, not a verified continuous cooling circuit. Fluid service requires an expressly designed passage, pressure boundary, sealing arrangement and appropriate pressure and leak testing.
No universal rating can be assigned from its appearance or copper grade. Ratings depend on dimensions, contact design, insulation, cooling and operating conditions, supported by the applicable assembly-level verification.
Request a Quote
Please provide the component drawing and mating-interface requirements for technical review.
| Required Information | Details to Provide |
|---|---|
| Drawing | Dimensioned PDF and, where available, a STEP or other suitable CAD file |
| Material | Copper grade, applicable material standard and required temper |
| Blade Geometry | Length, width, thickness, corner radii and mating contact details |
| Flange and Studs | Flange dimensions, stud spacing, shoulder geometry and datum surfaces |
| External Threads | Thread standard, size, pitch, fit, engagement length and coating condition |
| Internal Threads | Size, pitch, fit, depth and minimum remaining wall requirements |
| Functional Requirements | Installation torque, mechanical loads, current duty and operating temperature |
| Surface Treatment | Bare copper or specified coating system, thickness, coverage and masking |
| Inspection | Critical tolerances, roughness, testing, inspection frequency and documents |
| Quantity | Prototype quantity, batch quantity and expected repeat demand |
| Delivery Requirements | Destination country, packaging requirements and requested delivery schedule |
Contact Cymber Metalwith your drawing, quantity and application details to request a technical review and quotation.